9.5.2. entering the K factor or having it determined by teach-in

During the whole teach-in procedure, the outputs are frozen to the status they had at the start of the teach-in.

ENTER

0......9

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

0......9

0......9

*

*

KFAC

NO

TEAC

YES

TEAC

49.03

KFAC

TEAC

200.0

VOL

49.03

KFAC

To function OUT

* to move the decimal point, simultaneously press keys

0......9

and

• Entering the K factor of the fitting used:

→

select "NO TEAC",

→

press key "ENTER",

→

In the KFAC parameter, enter the K factor of the
fitting used, in pulse/litre (value between 0,001 and
9999). Find the K factor within the operating instruc-
tions of the fitting.

• Determining the K factor by means of a teach-in

procedure:

→

install the 8032 / 8072 in series with a valve, for
instance, then

→

fill a tank with x litres capacity (200 litres for
example).

→

select "YES TEAC",

→

press key "ENTER",

→

open the valve: message "TEAC" blinks.

→

when the tank if full, press again key "ENTER".

→

enter the volume of liquid that has passed through
the circuit (in the unit displayed alternately with the
message "VOL"): the device calculates the K factor
and displays it.