DescripTion

5.1.

Area of application

The compact version of the flowmeter type 8025 or 8035 is designed to measure the flow rate of a liquid and to totalise the
volume of a liquid.
The remote version of the flowmeter type 8025 is a transmitter that must be connected to an 8020 or an 8030 flow sensor with
a sinus or a pulse output, only in "Low Power" version.

5.2.

General description

The 8025 is a flowmeter available in compact, panel or wall-mounted version. The 8035 is a flowmeter in compact version.
• A compact version of the 8025 is composed of a flow sensor with paddle-wheel and of an electronic module (the electronic

is located in a housing with cover, display and 2 cable glands).

• A compact version of the 8035 is composed of a sensor-fitting type S030, with paddle-wheel and of an electronic module

(the electronic is located in a housing with cover, display and 2 cable glands).

• A panel version of the 8025 is an electronic module (an electronic located in an open housing with display).
• A wall-mounted version of the 8025 is an electronic module (an electronic integrated in a housing with cover, display and 3

cable glands).

According to the version, the device requires a 12-36 V DC or a 115/230 V AC power supply.
The electrical connection is carried out via a male fixed connector or on the terminal blocks of the electronic board: whether
directly, whether via 2 or 3 cable glands.

5.3.

measuring principle

The circulation of fluid within the pipe causes the paddle wheel of the sensor to rotate. The flowmeter detects the rotation of
the paddle-wheel and generates a signal which frequency f is proportional to the flow rate Q, using the formula f = KxQ.
f = frequency in Hertz (Hz)
K = K factor of the S020 or S030 fitting used, in pulse/litre
Q = flow rate in litre/second

5.4.

Available versions of the 8025 compact flowmeter

All the compact versions of the flowmeter 8025 have:
- a 4-20 mA current output;
- a pulse output ;
- two totalizers.

supply voltage

seals

electrical connection

relays

sensor

order code

12-36 V DC

FKM

1)

Male fixed connector

-

Hall, short

418762

12-36 V DC

FKM

1)

-

Hall, long

418763

12-36 V DC

FKM

1)

Male fixed connector

-

Coil, short

418764

12-36 V DC

FKM

1)

-

Coil, long

418765

12-36 V DC

FKM

1)

Terminal strips via 2 cable
glands

-

Hall, short

418802

12-36 V DC

FKM

1)

-

Hall, long

418803

12-36 V DC

FKM

1)

Terminal strips via 2 cable
glands

-

Coil, short

418804

12-36 V DC

FKM

1)

-

Coil, long

418805

12-36 V DC

FKM

1)

Terminal strips via 2 cable
glands

2

Hall, short

418778

12-36 V DC

FKM

1)

2

Hall, long

418779

12-36 V DC

FKM

1)

Terminal strips via 2 cable
glands

2

Coil, short

418780

12-36 V DC

FKM

1)

2

Coil, long

418781

115/230 V AC

FKM

1)

Terminal strips via 2 cable
glands

-

Hall, short

418423

115/230 V AC

FKM

1)

-

Hall, long

418424

English