English – Burkert Type 3005 User Manual
Page 21

21
Installation
→
Connect cable according to the required control type to the terminal
strip Pos. B of the power supply circuit board.
operating principle for open / closed mode:
• Switch open = actuator closes
• Switch closed = actuator opens
connecting feedback
The limit switches for the feedback are suitable for a
maximum voltage of 250 V AC/DC - 5 A.
The rotary actuator features two additional limit switch contacts which
are supplied by the factory in an open position. These can be used for
the feedback of the rotary actuator.
2
3
1
FC2
FC1
FCF
FC0
4-6
5
7
=
C
C
A
B
D
D
T/E
Feedback
Power supply and control
Motor
Fig. 20: Internal wiring of actuator
The limit switch contacts are actuated via two cams no. 13 (see
Fig. 1 and Fig. 2).
• The white cam is used to record the opening process (FC1).
• The black cam is used to record the closing process (FC2).
procedure:
→
Connect cable to the terminal strip 12 (see “Fig. 1” and “Fig. 2”)
according to the schematic (see “Fig. 20”).
english
Type 3005