Start-Up

specify end positions

R

→

Press <MEM> and <OPEN> push-
buttons to save the open position.

The GREEN LED lights up 2x.
All positions are now saved.

→

Disconnect the card from the power
supply.

9.3.3. normal operation

Display normal operation

G

→

Switch on card.

The GREEN LED lights up 3x to indicate that the start
process has been implemented correctly.

G

In normal operation the GREEN LED lights up when the
rotary actuator opens the shut-off valve.

R

The RED LED lights up when the rotary actuator closes
the shut-off valve.

G

R

If neither of the LED’s is lit, the actuator is not actuated.

G

R

The RED and the GREEN LED’s light up if the torque
is too high and the rotary actuator stops.

→

Change direction of rotation of the rotary actuator
or switch over the voltage OPEN/CLOSED to
restart the rotary actuator!

10. start-up

Warning!

Danger due to improper operation!
Improper operation may result in injuries as well as damage to the
device and the area around it.
• Before start-up, ensure that the operating personnel are familiar

with and completely understand the contents of the operating

instructions.

• In particular observe the safety instructions and intended use.
• The device/the system may be started by adequately trained

personnel only.

Procedure:

→

Ensure that connections and settings are implemented properly
according to chapter “8. Installation”.

→

Check whether the rotary actuator and the fitting are in a defined
end position, otherwise the fitting may lock. In this case the
actuator switches off automatically.