Burkert Type 3005 User Manual

Page 32

Advertising
background image

32

Installation

learning mode

specify end positions

G

R

→

Press <OPEN> and <CLOSE> push-buttons and switch on the card
(hold down push-button).

The RED and the GREEN LEDs light up.

→

Release <OPEN> and <CLOSE> push-buttons.

Both LEDs go out.

Learning mode is selected.

R

→

Press <CLOSE> push-button to move the shut-off valve into the
closed position.

The RED LED lights up.

R

→

Press <MEM> and <CLOSE> push-buttons to save the closed
position.

The RED LED lights up 2x.

G

→

Press <OPEN> push-button to move the shut-off valve into the open
position.

The GREEN LED lights up.

R

→

Press <MEM> and <OPEN> push-buttons to save the open position.

The GREEN LED lights up 2x.

All positions are now saved.

→

Disconnect the card from the power supply.

8.3.3.

normal operation

Display normal operation

G

→

Switch on card.

The GREEN LED lights up 3x to indicate that the start process has been
implemented correctly.

G

In normal operation the GREEN LED lights up when the rotary actuator
opens the shut-off valve.

R

The RED LED lights up when the rotary actuator closes the shut-off valve.

G

R

If neither of the LEDs is lit, the actuator is not actuated.

G

R

The RED and the GREEN LEDs light up if the torque is too high and the
rotary actuator stops.

→

Change direction of rotation of the rotary actuator or switch over the
voltage OPEN/CLOSED to restart the rotary actuator!