40

Maintenance,Troubleshooting

malfunction

remedial action

The valve does not fully open or close

→

Check the power supply.

→

Check the connections according to the supplied circuit
diagram.

→

Check the limit switches.

→

Check whether an overload has occurred due to excessively
high torque on the valve (our rotary actuators feature electronic
overload protection).

if yes: Interrupt the power supply for approx. 5 minutes.

The rotary actuator is jammed in the
CLOSED position

→

Check the power supply.

→

Check the connections according to the supplied circuit
diagram.

→

Check whether the movement of the electric valve is obstructed.