Burkert Type 8112 User Manual

Page 27

Advertising
background image

-

Pipe thread, cylindrical (DIN 3852-A)

G¾ A, G1 A

-

American pipe thread, conical
(ASME B1.20.1)

¾ NPT

or 1 NPT

-

Flanges

DIN from DN 25, ANSI from 1"

-

hygienic fittings

Bolting DN 40 PN 40, Clamp 1" DIN 32676
ISO

2852/316L, Clamp 1½" PN 10 DIN 32676

ISO

2852/316L, conus DN 25 PN 40, Tuchenhagen

Varivent DN 50 PN 10

Max. torque - process fitting

-

Thread G¾ A, ¾ NPT

75 Nm (55 lbf ft)

-

Thread G1 A, 1 NPT

100 Nm (73 lbf ft)

High voltage test (enamel)

max. 5 KV

Gas-tight leadthrough (optional)

-

Leakage rate

< 10

-6

mbar l/s

-

Pressure resistance

PN

64

Output variable

Output

Two-wire NAMUR output

Current consumption

-

Falling characteristics

≥ 2

.6 mA uncovered/≤ 0.6 mA covered

-

rising characteristics

≤ 0

.6 mA uncovered/≥ 2.6 mA covered

-

Fault message

≤ 0

.6 mA

Necessary processing system

NAMUR processing system according to
IEC

60947-5-6 (EN 50227/DIN 19234)

Modes (NAMUR output adjustable to falling or rising characteristics)

-

Min.

rising characteristic curve (High current when
immersed)

-

Max.

falling characteristics (Low current when immersed)

Measuring accuracy

Deviation

± 1

mm (0.04 in)

LEVEL SWITCH

8112 • with NAMUR output

27

9 Supplement

32052

-

EN

-

120418