Fluid Components International ST98 Modbus Module ebloxx A1-1 User Manual

Fluid Components International Equipment

Advertising
background image

Company Headquarters: 1755 La Costa Meadows Drive, San Marcos,

CA 92069-5187

DOCUMENT NUMBER

06EN003371

SUBJECT

Users Guide – ST98 Modbus

CAGE CODE

64818

DATE

02/03/05

SECTION

PAGE

1 of 3

REVISION

-.

1.0 SCOPE

This document is a supplement to instructions that use the e.BLOXX A1 communication module. It
provides information on the instruction set used by the module. The e.BLOXX A1 module converts
the current output of an FCI instrument into a Modbus RTU signal.

2.0 APPLICABLILITY

The instructions and information found in this document are applicable to the ST98 with the
e.BLOXX A1 module.

3.0 INSTALLATION


3.1 MODBUS CONNECTIONS

The ST98 MODBUS data transfer is based on the RS485 Standard and EN50170. When

planning the Installation it is recommended that the physical regulation for RS485 equipment
be followed.

See Figure below for recommended connection to MODBUS network.




A Line


B line
















MODBUS CABLE


The ST98 with the E.BLOXX module has no integrated terminating resistors . An
external termination resistor network needs to be added at the end of segment is the ST98 is the
last instrument in the segment.





NOTICE OF PROPRIETARY RIGHTS: THIS DOCUMENT CONTAINS CONFIDENTIAL TECHNICAL DATA, INCLUDING TRADE SECRETS AND
PROPRIETY INFORMATION WHICH IS THE PROPERTY OF FLUID COMPONENTS INTERNATIONAL LLC (FCI).

Advertising