Operating elite steam, 1 displaying information, 1 select signal type – GeneralAire DS35 Elite Steam User Manual

Page 18: 3 activating manual drain, 4 resetting the hour counter, 2 changing the maximum production

Advertising
background image

18

Elite Steam +03U221903 REV 2.1

Fig. 5.a

5.1 Displaying Information

By pressing the “Reset” button for 2 seconds, the display will loop from amperage to production in %

of the maximum production to the hour counter and back to amperage:

1. Amperage: the value of the current that flows through the water making it boil off

(default display)

2

. Production %: the current production expressed as a percentage of the

capacity

.

3. Hour counter, expressed in tens: for instance, when the display shows 13 the real hour

value will be between 130 and 139 hours.

5.1.1 Select Signal Type

The Elite Steam is preset for the included E Series humidistat (signal type 0). If the included humidistat is used,

this section may be omitted. If another humidistat is used, review this section to see if changes are needed.

1. Switch Elite Steam off.

2

. Press and hold both buttons “reset” and “drain” and switch Elite Steam back on.

When the wrench blinks,

release the 2 buttons.

3. Press “Reset” until the display shows 02. WARNING: DO NOT confirm any

value higher than 04. In case, press “Reset” until the display goes back to the normal

operating mode and restart from step 1.

4. Press “drain” (minimum 1 second) to confirm: the display shows “P1” then the current signal

type and “set”.

1. Switch Elite Steam off.

2.. Press both and hold both buttons “Reset” and “Drain” , and switch Elite Steam back on. When the

4

. Press “drain” (minimum 1 second) the display shows “P0” then the current Maximum Production

Percent and "set".

5. Press “reset” to change the Maximum Production in steps of 5% between 20% and 100%.

6. Press and hold “drain” (minimum 1 second) when done to confirm the new Maximum Production

and exit to the normal operating mode.

5.3 Activating Manual Drain

Press and hold the “drain” button on the front of the unit until the cylinder is drained. Note: Water will

continue to flow from the tempering valve after the cylinder is empty.

5.4 Resetting the hour counter

The hour counter should be reset every time the cylinder is changed in order to reset and restart the

internal maintenance timer:

1. Switch Elite Steam off.

2

. Press and hold both buttons “Reset” and “Drain” and switch Elite Steam back on. When the

wrench

blinks; release buttons.

3. Press and hold “reset” until the display shows 03. WARNING: DO NOT confirm any

value higher than 04. In case, press “Reset” until the display goes back to the normal

operating mode and restart from step 1.

4.

Press “Drain” (mininimum 1 second) to confirm: the hour counter will be reset at once and

Elite Steam will go back to the normal operating mode.

5. OPERATING ELITE STEAM

5.2 Changing The Maximum Production

wrench blinks;

release the 2 buttons.

3. Press “reset” until the display shows 01. WARNING: DO NOT confirm any value higher than 04. In

case, press "Reset" until the display goes back to the normal operating mode and restart from step 1.

5

. Press “Reset” to change signal type between 0 and 1:

0 = On-Off humidistat such as the GeneralAire “M” or “E” series humidistat.

1 = external 0...10 Vdc modulating signal such as the GeneralAire ADCD series humidistat.

6. Press “drain” (mininimum 1 second) when done to confirm the new value of P1 and exit to the

normal operating mode.

7. Switch Elite Steam off: you can now proceed with connecting the control wiring.

The maximum production can be adjusted between 20% to 100% of the humidifier's capacity in steps of 5% in

order to suit the environment characteristics. DS35 and RS35 Maximum production is factory set at 70%.

Advertising