Elite Steam +03U221903 REV 2.1

Problem

Causes

Solutions

The humidifier does not

turn on

1 No electrical power

2

. On/off switch of the humidifier in

Position 0 (off)

3. Control connectors improperly connected

4

. Blown fuses

5. Transformer failure

1. Check the safety devices upstream from the humidifier

and the presence of power

2

. Close the switch on the panel: position I

3. Check that connectors are properly inserted in terminal block

4

. Check the condition of fuses

5. Check that the proper voltage is connected and turned on

The humidifier does not

start operation

1. Remote ON/OFF contact open

2

. The humidistat has not been

connected correctly

3. Humidistat failure

4

. Control signal not compatible with

the type set

5. Value measured by the sensors higher

than the corresponding set point

1. Close ON/OFF contacts

2

. Check the external connection

3. Replace the humidistat

The humidifier fills with

water without producing

steam

1. High steam back pressure

2

. Fill valve strainer clogged

3. Mineral in the fill cup

4

. Drain solenoid valve leaking

1. Check that the steam hose is not kinked or sagging,

trapping condensate

2

. Clean the fill valve strainer

3. Clean the fill cup

4

. Check for voltage at the drain solenoid valve and/or drain

solenoid replacement

The humidifier wets

the duct

1. The distributor is not installed correctly

(too near the top of the duct or the

condensate return is blocked)

2

. System over-sized

3. Humidifier active when the fan in the

duct is off

1. Check that the steam distributor is installed correctly

2. Decrease the steam production set on the control

3. Check the connection of the device (flow switch or differential

pressure switch)

the duct.

controling the humidifier to the ventilation in

The humidifier wets the

floor below

1. The humidifier drain is blocked

2. The supply water or overflow circuit has

leaks

3. The condensate drain pipe does not

bring the water back to the drain pan

4. The steam hose is not properly fastened

to the cylinder

1. Clean the drain assembly and pan

2. Check the entire water circuit

3. Check the correct position of the condensate drain hose in the

drain pan

4. Check the fastening of the hose clamps on the steam outlet

Tab. 6.a

Problem

Causes

Solutions

Water in the cylinder

turns black

1. Minerals in the cylinder have over

concentrated and are deteriorating the

electrodes

1. Check for sags & kinks that could trap condensate in the

steam hoses that could cause a back pressure on the cylinder

2

. Check the duct static pressure

3. Check the fill valve and inlet strainer

4

. Check the drain valve operation

5. Correct installation problems and replace cylinder

Heavy arcing occurs

within hours of startup

1. The feed water contains large amounts

of Iron, Copper or, other conductive

contaminants

1. Contact the factory for an optional drain timer to force

additional drains to control the minerals

2

. If you are using a softener, check the salt being used. If it

contains any additives, discontinue use, flush all lines and

convert to pure salt or unsoftened water

3. Check the electrodes in the cylinder to be sure they were not

damaged in shipping

Humidifier continuously

fills and drains without

production steam

1. Minerals have bridged the electrodes

2

. There is back pressure from the steam

hoses or duct

3. The flow regulator in the fill valve is broken

or out of place

4

. Water conductivity is very high

5. Water is foaming excessively

1. Clean or replace the cylinder

2

. Check the steam hoses for kinks or gullies that might be

trapping condensate

3. Replace the fill valve

4

. Consider using a mix of demineralized water with raw water

5. Check cylinder - replace if exhausted. If feed water contains

silica or nitrates, install a 1 micron water filter

Tab. 6.b