6 alarms, 5 using the e2 humidistat 5 – GeneralAire DS35 Elite Steam User Manual

Page 19

Advertising
background image

Elite Steam +03U221903 REV 2.1

Display

Description

Action

Red

Alarm

Relay

Notes

- -

Remote on-off open

Unit disabled

Off

Off

Check AB-AB jumper or pres. switch

EE

Internal memory error Unit disabled

On On Contact Tech. Support

E0

Control board configuration not valid

Unit disabled

On

On

E1

High current alarm

Unit disabled

On

Turn off, check connections, check cylinder

(no limescale bridges between electrodes,

no electrodes short-circuited)

E2

Low production, low supply water conductivity

excessive foam/limescale in the cylinder

Unit disabled

Press “reset” key for 1 seconds to reset.

On

On

Check supply water conductivity (too low?),

replace the cylinder.

E3

Cylinder lifetime expired

(1200 hours)

Press “reset” key for 1 seconds to reset.

The warning will be displayed 50 hrs later

until the hour counter is reset and the

cylinder replaced.

Off

Off Change cylinder (not urgent)

E4

Fill alarm, unable or slow fill

(current does not increase within

timeout)

Press “reset” key for 1 seconds to reset,

otherwise the warning will be reset aut -

o

-

matically every 10 minutes until the supply

water is available again.

0n

On Check water supply and fill valve;

check drain valve for leakage

E5

Drain alarm, unable to drain

(current does not decrease within timeout)

Press “reset” key for 1 seconds to reset

On

On Check drain valve and drain connection

E6

Cylinder exhausted

(critical performance detected)

The warning is automatically reset if

CompactSteam can produce the demand,

Off

Off

Change cylinder (urgent)

E7

Foam detected

Press “reset/sel” key for 1 seconds to reset

Off

Off

If it continues, do some cleaning cycles

(read

chap. “Starting with a new cylinder”)

E8

High Controller Temperature

(2000 hours)

Reset the hour counter (read chapter

Resetting the hour counter”)

Off

Off

Change the cylinder.

E9

(above 80°C / 176

°F )

The warning is automatically reset if the

temperature decreases below 80°C / 176 °F.

Off

Off Check the ambient temperature,

replace the controller.

Tab. 5.a

5.6 Alarms

In the event of an alarm, the red alarm LED will flash, the alarm relay will close, and the alarm code will flash in the display.

Multiple alarms will flash in sequence, alternating with the main display. Pressing the sel button for 2 seconds will reset

the alarms, although still active alarms will continue to display.

.

5 Using the E2 Humidistat

5

Press to select

OFF, MANUAL or

AUTO mode (if outdoor sensor is connected)

.

OFF mode: The humidifier is turned off.

Suggested Setting Outdoor Temperatures

AUTO mode: The E2 will automatically raise the humidity as the outdoor temperature increases. This provides the highest

NOTE: If the outdoor temperature sensor fails,

flashes and the unit will default to

MANUAL mode.

.

To toggle between indoor / outdoor temperature and indoor humidity: Press .

To change the temperature unit: Press °C / °F

.

To set the temperature / humidity offset in MANUAL or AUTO mode:

1. Simultaneously press and

when viewing the temperature or humidity reading.

2. Use

or

to change the setting (-3 to 3).

3. Press

and

simultaneously or wait 5 seconds to confirm and move onto the next setting.

Lo or Hi will flash on the display when:

MEASUREMENT LO

HI

Indoor temp.

Below 0

o

C

(32

Above

99

o

F(37

o

C)

Outdoor temp.

Below -40

o

C

(-40

o

F)

Above 50

o

C

(122

o

F)

Humidity

Below 10%

Above 90%

• If power is lost, current settings are retained.

WARNING

Do not allow excess humidification. Excess humidity can cause condensation and enable mold and mildew growth.

15%

20%

25%

30%

35%

40%

-20F

-10F

0 F

+10F

+20F

+30F

-29C

-23C

-18C

-12C

-7C

-1C

possible humidity. The E2 will automatically lower the humidity as temperatures drop. This minimizes the risk of condensation ON

on cold surfaces like windows. You can adjust the Auto Humidity Index Set Point from 0(low) to 10(high) by pressing

or

The Humidity Index is based on the outdoor temperature and indoor humidity. The humidity will switch ON/OFF according

to the calculated auto humidity index set point. Lower index settings are for older homes with less insulation and vapor barriers.

Higher Index settings are for newer homes with complete vapor barriers, triple pane windows, and high R value insulation.

If condensation occurs reduce Index setting by 2 points until condensation stops.

.

F)

o

Led

Cylinder lifetime expired

19

On

Contact Tech. Support

MANUAL mode: The E2 will work to maintain the single humidity selected.

You can set your desired humidity level by pressing or . The humidi-

fier will turn ON or OFF according to your manual setting. (The humidifier

will operate when the measured relative humidity falls more than 2% below

the set point). Humidity will have to be lowered when weather is colder or if

condensation is suspected.

Advertising