Master programming mode – Hydrotech SXT Timer User Manual

Page 5

Advertising
background image

MASTER PROGRAMMING MODE

When the Master Programming Mode is entered, all available

option setting displays may be viewed and set as needed.

Depending on current option settings, some parameters cannot

be viewed or set.

Setting the Time of Day
1. Press and hold either the Up or Down buttons until the

programming icon replaces the service icon and the

parameter display reads DO.

2. Adjust the displayed time with the Up and Down buttons.
3. When the desired time is set, press the Extra Cycle button

to resume normal operation. The unit will also return to

normal operation after 5 seconds if no buttons are pressed.

Entering Master Programming Mode
Set the Time Of Day display to 12:01 P.M. Press the Extra

Cycle button (to exit Setting Time of Day mode). Then

press and hold the Up and Down buttons together until the

programming icon replaces the service icon and the Display

Format screen appears.

Exiting Master Programming Mode
Press the Extra Cycle button to accept the displayed settings

and cycle to the next parameter. Press the Extra Cycle

button at the last parameter to save all settings and return to

normal operation. The control will automatically disregard any

programming changes and return to normal operation if it is

left in Master Programming mode for 5 minutes without any

keypad input.

Resets
Soft Reset:
Press and hold the Extra Cycle and Down buttons

for 25 seconds while in normal Service mode. This resets all

parameters to the system default values, except the volume

remaining in meter immediate or meter delayed systems and

days since regeneration in the time clock system.
Master Reset: Hold the Extra Cycle button while powering up

the unit. This resets all of the parameters in the unit. Check

and verify the choices selected in Master Programming Mode.

1. Display Format (Display Code DF)

This is the first screen that appears when entering Master

Programming Mode. The Display Format setting specifies

the unit of measure that will be used for volume and how

the control will display the Time of Day. This option setting is

identified by “DF” in the upper left hand corner of the screen.

There are three possible settings:

Display Format Setting

Unit of Volume

Time Display

GAL

U.S. Gallons

12-Hour AM/PM

Ltr

Liters

24-Hour

2. Valve Type (Display Code VT)

Press the Extra Cycle button. Use this display to set the

Valve Type. The Valve Type setting specifies the type of

cycle that the valve follows during regeneration. Note that

some valve types require that the valve be built with specific

subcomponents. Ensure the valve is configured properly before

changing the Valve Type setting. This option setting is identified

by “VT” in the upper left hand corner of the screen. There are 5

possible settings:

Abbreviation

Parameter

dF1b

Standard Downflow/Upflow, Single Backwash

dF2b

Standard Downflow/Upflow, Double Backwash

Fltr

Filter

UFbd

Upflow Brine First

8500

TwinFlo 100

Othr

Other

3. Control Type (Display Code CT)

Press the Extra Cycle button. Use this display to set the

Control Type. This specifies how the control determines when

to trigger a regeneration. For details on how the various

options function, refer to the “Timer Operation” section of this

service manual. This option setting is identified by “CT” in the

upper left hand corner of the screen. There are four possible

settings:
Meter Delayed:

Fd

Meter Immediate:

FI

Time Clock:

tc

Day of Week:

dAY

4. Number of Tanks (Display Code NT)

Press the Extra Cycle button. Use this display to set the

Number of Tanks in your system. This option setting is

identified by “NT” in the upper left hand corner of the screen.

There are two possible settings:
Single Tank System: 1
Two-Tank System: 2

Fleck SXT Timer JL10 • 5