Operation, To the (-) terminal, Figure 1 – Hach-Lange SC 200 Active 4-20 mA Output Module User Manual User Manual

Page 5: Figure 2, External loop resistance may be required, Table 3, Table 4

Advertising
background image

Figure 1 Wiring diagram for external customer powered

1 4–20 mA output module

3 Customer power supply

2 External device (Recorder/data

acquisition system)

Table 3 Resistance values for external customer powered

Power supply voltage

Loop minimal
resistance

Loop maximal
resistance

12–18 VDC

0 Ω

250 Ω typical

18–24 VDC

250 Ω

500 Ω typical

Figure 2 Wiring diagram for module powered

1 4–20 mA output module

2 External device (HART master)

Table 4 Resistance values for module powered

Power supply voltage

Loop minimal
resistance

Loop maximal
resistance

15 VDC

0 Ω

350 Ω typical

English 5

Advertising