Figure 4, Table 4, Figure 5 – Hach-Lange POLYMETRON 9586 User Manual

Page 18

Advertising
background image

Figure 4 Discrete input wiring connections

Table 4 Input connections

Discrete inputs

Connector position - Switch input

Connector position - Voltage

input

Input 1+

3

2

Input 1-

2

3

Input 2+

6

5

Input 2-

5

6

Input 3+

8

7

Input 3-

7

8

Figure 5 Jumper settings

1 Input 1 configuration jumpers

3 Input 3 configuration jumpers

5 Jumpers positioned to the right

for voltage inputs

2 Input 2 configuration jumpers

4 Jumpers positioned to the left for

switch inputs

1. Open the controller cover.
2. Feed the wires through the cable gland.
3. Adjust the wire as necessary and tighten the cable gland.
4. The jumpers are positioned immediately behind the connector. Remove the connector for

improved access to the jumpers and configure the jumper settings according to the type of input
as shown in

Figure 5

.

5. Close the controller cover and tighten the cover screws.
6. Configure inputs in the controller.

16 English

Advertising