MAN-13262

R

EV

BA

DIN

R

AIL

A

MPLIFIER

,

MWI-13262

U

LTRA

J1

Figure 4 - Internal Jumper-switches and Potentiometer Location

2.5 C

ONFIGURING THE

S

WITCH

S

ETTINGS

A number of operational characteristics can be configured prior to mounting or wiring the amplifier. We
recommended that you first familiarize yourself with the internal switch locations, settings, and potentiometers by
opening the snap-on access cover. Figure 4 illustrates the location of configurable items on each of the printed
circuit boards.

Use an approved anti-static wrist strap when adjusting any switch settings/potentiometers on the amplifier.

Switch

PCB Location

Function

J3

Input

Configures Excitation voltage for 5.0 or 10.0 VDC. The amplifier is factory set at (setting 1-2 ) for
5.0V

J8

Input

Selects left channel only (setting 2-3) or LCH + RCH (setting 1-2) as input to summing amplifier
stage. Slide the jumper switch to (1-2) for normal operation with two transducers. Refer to
setup/calibration section for more information.

J1

Input

Connects completion resistances of RCH transducer input to ½ of excitation voltage
(setting 1-2). Slide the jumper switch to setting (2-3) for normal operation with Ultra Full-Bridge
transducers. Slide jumper switch to setting (1-2) if the channel is unused.

J2

Input

Connects Completion resistances of LCH transducer input to ½ of excitation voltage
(setting 1-2). Slide the jumper switch to setting (2-3) for normal operation with Ultra Full-Bridge. Slide
the jumper switch to setting (1-2 ) if the channel is unused.

J10
J9
J7

Input

Sets voltage gain of LCH Instrumentation amplifier to 5, 25, 125 or 620. The jumper switches are
factory set to (1-2) for minimum gain (Av = 5). Refer to section 2.9 for more information on setting
Gain select switches.

J6
J5
J4

Input

Sets the fixed gain of RCH Instrumentation amplifier. The jumper switches are factory set to
(1-2) for minimum gain (Av=8).

J1

Output

Configures meter output stage for +/- 2V F.S. or +/- 1 mA F.S. The jumper switch is factory set to (1-
2 ) for voltage output. Voltage and current modes use different terminals.

J2

Output

Selects meter damping 0.3 Hz or 3.7 Hz. The jumper switch is set to (2-3) for minimum damping. (3.7
Hz)

Output
Board

J10

J9 J7

J5

J6

J4

P5
LCH Course
Zero

P4
Balance

P3
RCH Course
Zero

Input
Board

J2

J1

J8
Channel
Select

J3

J2

LCH Gain

RCH Gain

P

AGE

11