Controlled Products Systems Group 26SASM User Manual
Page 7

SETTING THE SYSTEM (FACILITY) CODE
When received, the correct system code may already be set. Should it
become necessary to reset the system code, remove the unit from the
wall to gain access to the reset button (see figure 1). Momentarily depress
the reset button. The LED indicator will flash red and green alternately
(If at power up, the LED is already flashing red/green, it is not necessary
to remove the unit from the wall and press the reset button). While the
LED indicator is flashing, place either a programming card or an access
card with the proper system code onto the touch plate and after the LED
turns solid Green, remove it. The ENTRACOMP
®
26SA will “remember”
the system code and retain it until reprogrammed. If the reset button is
pushed, but no card is placed on the TOUCH CARD
®
reader plate before
the LED indicator times out, the system code will be unchanged. Wait
for the LED indicator to time out before programming the unit.
There may occur situations which require the unit to recognize more
than one system (facility) code. The ENTRACOMP
®
26SA can be set
to recognize up to ten (10) different system codes. To program multiple
system codes, follow the procedure above for programming a single
system code, but place a card with the second system code (and third
system code if necessary) on the TOUCH CARD
®
reader plate before the
red/green LED indicator times out. When more than one facility code
has been programmed, the unit will not distinguish between cards
having different facility codes but the same ID number.
Secura Key • 3