Wiring Options

I/O Wiring – SeaDAC Lite 8111 - 8115 Modules

Depending on model, you can control and monitor up to 4 optically isolated inputs
and 4 Reed or Form C relay outputs. Each Reed or Form C relay has a discrete
common (ground) and each pair of inputs share a common. Reed relays can switch
up to 60VDC @ 500mA, while Form C relays can switch up to 100VDC @ 5A or
250VAC @ 6A. The non-polarized input voltage range is 5-30VDC and features
300V optical isolation to protect the host computer from damaging voltage transients
and ground loops commonly found in industrial environments.
Field wiring is simplified via 3.5mm removable screw terminal blocks with optional
spring clamp terminal blocks also available. The removable terminal blocks are
compatible with 14-22 AWG field wiring.