SP3850 Flow Computer
SETUP RELAYS
Rly1
Rly2 Rly3 Rly4
RELAY 1 USAGE
RATE TOTAL NA
RELAY 1 DELAY sec
0
RELAY 1 MODE
LO_ALARM HI_ALARM
RELAY 1 DURATION
#####
RELAY 1 SETPOINT
####### gal
RELAY 1 HYSTERESIS
##### gal/m
Advance To
SETUP RELAYS 3, 4
Sub-menus
Display
Notes
ENTER
ENTER
ENTER
ENTER
ENTER
6.3.14
SETUP RELAYS
(Relay 1 & Relay 2)
ENTER
Select the desired Relay for setup.
(Relays 3 & 4 Optional)
If Relay 1 or Relay 2 Selected,
Select Rate, Total or NA.
If Rate selected, enter desired relay activation
delay value.
Select the desired Relay Activation.
Low: Relay activates when reading is below
setpoint.
High:Relay activates when reading is above
setpoint.
If Total Selected, Enter desired Relay
Duration.
Enter the desired Setpoint. The Setpoint can
be edited in run mode using the PRE 1 key
(PRE 2 key for Relay 2).
If Rate, selected, Enter desired Relay
Hysteresis.
NOTE:
In Batch mode,
Relay 1 is reserved
for Preset,
Relay 2 is reserved
for Prewarn.
ENTER