3.4.1.6 SAMPLE HAND HELD CONFIGURER COMMANDS
The following table provides a sample of typical Hand Held Configurer Display (D ), Put (P ), and
Memory Transfer (T ) commands.
Key Entries
Displayed Data
Result
D B021 <ENTER>
D B021 XXX
Displays contents of B021.
D N <ENTER>
D B022 XXX
Displays contents of B022.
D <ENTER>
D B022 XXX
B022 contents still displayed.
P C256 <ENTER> 200 <ENTER>
P C256 200
Alters contents of C256 to 200.
P <ENTER>150 <ENTER>
P C256 150
Alters contents of C256 to 150.
P N 200 <ENTER>
P C257 200
Alters contents of C257 to 200.
T <ENTER>
MEMORY TRANSFER
F1 - TO CONTROLLER
F2 - FROM CONTROLLER
F
F
F
TRANSFER FINISHED
Displays memory transfer query
to either send database
information (or analog
constants) to the instrument, or
receive database information
(or analog constants) from the
instrument.
Note: XXX = Displayed characters from addressed datapoint.