Single Loop Process Controller Instruction Manual
136 Database
ANI1
Calibrate
Zero
CIZ
B264
This is the calibration zero adjustment. This parameter is
factory set and should not need adjustment under
normal operation. See
for adjustment.
ANO0
Calibrate
Zero
COZ
B267
This is the calibration zero adjustment. This parameter is
factory set and should not need adjustment under
normal operation. See
for adjustment.
ANI0 Digital
Filter Index
DFILT
B269
3
This controls a first order filter that is applied to the input
signal. The time constant is entered as an index value as
follows:
0 - No Smoothing (no effect)
1 - 0.05 s
2 - 0.1 s
3 - 0.3 s
4 - 0.7 s
5 - 1.5 s
6 - 3.1 s
7 - 6.3 s
8 - 12.7 s
9 - 25.5 s
10 - 51.1 s
11 - 102 s
12 - 205 s
13 - 410 s
14 - 819 s
15 - 1638 s
ANI1 Digital
Filter Index
DFILT
B270
3
This controls a first order filter that is applied to the input
signal. The time constant is entered as an index value as
follows:
0 - No Smoothing (no effect)
1 - 0.05 s
2 - 0.1 s
3 - 0.3 s
4 - 0.7 s
5 - 1.5 s
6 - 3.1 s
7 - 6.3 s
8 - 12.7 s
9 - 25.5 s
10 - 51.1 s
11 - 102 s
12 - 205 s
13 - 410 s
14 - 819 s
15 - 1638 s