Micromod MOD: 30ML and Modcell Totalization Application Guide User Manual
Page 18

Using The Totalizer Block
Building the Strategy
16
Table 3. Edit Inputs Data, PIDDISP Block
Input
No.
Input Name
Type
Line
Format
I10
TOTAL
Remote
1
TOTALL
1
Changes to Remote automatically happen when an external connection is made.
7. Close the Inputs menu by clicking on the red diamond in the upper left corner of the block.
8. Select
.
9. Enter the information from Table 4 into field format F8.
Table4. Edit Display Format Data, PIDDISP Block
Format
Name
Display
Format
Low
Limit
High limit
Entry
Method
TOTAL
Float0
0
10000000.0
None
10. Close the Display Formats menu by clicking on the red diamond in the upper left corner of
the block.
11. Select
.
12. Modify the existing Display block script to appear as that in Figure 3.
DEFAULTS:
{
MANUAL_PRESSED:
{
IF OPMS != 3 THEN
{
OPMS = 0;
#LINE5 = " OP";
#LINE6.SRC = OP;
}
}
AUTO_PRESSED:
{
IF OPMS != 3 THEN
OPMS = 1;
}
SCROLL_PRESSED:
{
IF SCRLCNT >= 2 THEN
SCRLCNT = 0;
ELSE SCRLCNT = SCRLCNT + 1;
CASE SCRLCNT OF
{
0:
#LINE5 = " OP";
#LINE6.SRC = OP;
BREAK;
1:
#LINE5 = " SP";
#LINE6.SRC = SP;