MOD 30ML Multiloop Controller
POWER, GROUNDING, AND BUILT-IN I/O CONNECTIONS
5. Use a small flat-head screwdriver to loosen appropriate connection screws and clamps
on terminal blocks.
6. Strip approximately 5/16 inch (8 mm) of insulation from the end of each wire, insert wires
at assigned terminals and secure terminal screws and clamps.
7. Make wiring connections using the following procedures:
a. Power connections - Section 3.3.
b. Ground and shield connections - Section 3.4.
c. Built-in process input connections for various types of inputs - Section 3.5
d. Built-in output connections - Section 3.6
8. After all connections are completed and checked, do the following:
a. If modular I/O and communications are required, follow the procedures in Sections 4
and 5.
b. If all connections are completed, the ac power wiring can be connected at the
distribution panel (ac source).
NOTE: Before putting the controller into operation, it must be configured using either the
front panel keys or the PC configuration Software. See Section 1.1.2 for related documents.
Instrument Common (terminal 25) should not be left floating. Tie it to chassis or a separate
instrument ground if available.