MOD 30ML Multiloop Controller

MODULAR I/O CONNECTIONS

4.3.7 2020N Remote I/O Interface Module (RIO) (discontinued)

Make remote I/O interface connections as shown in Figure 4-9. One remote I/O interface
module is required for each remote I/O network. The remote I/O interface module is scanned
every 50ms by the controller. A maximum of 2 RIO modules are allowed per instrument.
Specifications are:

REMOTE I/O INTERFACE RS485 SERIAL NETWORK

Bus Master

2020N Remote I/O Interface Module (end of bus)

Bus Slaves

Remote I/O Digital Modules

Maximum Length

500 meters (1600 feet)

Baud rate

187.5K

Max addresses

32 (31 slaves + 1 RIO master at address 0)

Termination

120 ohm resister is required across the two conductors
at the end of the cable (2 shipped with RIO module)

Shield

Required over 50 meters (160 feet)

REMOTE I/O INTERFACE CABLE

Indoor use

Belden #9182

Indoor plenum use

Belden #89182

Underground use

Belden #9815 twisted twinax

Outdoors above ground use

NOT recommended

Wiring

Use same cable type throughout network. Avoid
interruptions (wire to same terminals if necessary).

Do not wire through terminal blocks.


Table 4-3. Supported Remote I/O Modules (discontinued)

Module Description

Digital Input Modules .....................ICSI 08 D1 8 non-isolated 24VDC input channels

ICSI 08 E1 8 isolated 24VDC input channels
ICSI 08 E3 8 isolated 120VAC input channels
ICSI 16 D1 16 non-isolated 24VDC input channels
ICSI 16 E1 16 isolated 24VDC input channels


Digital Output Modules ..................ICSO 08 R1 8 relay output channels 2A

ICSO 08 Y1 8 transistor output channels 24VDC 2A


Digital Input/Output Modules ........ICSK 20 F1 12 non-isolated 24VDC input channels and 8 isolated

relay output channels

ICSC 08 L1 8 user-configurable channels for 24VDC input or

24VDC 500mA transistor output


* NOTE:

Modules are available in three forms: -120 for 110/120Vac external power, -230 for
220/230Vac external power and -24 for 24Vdc external power. All modules mount on a ECZ
remote I/O module carrier. See IB-23C601 for details on Remote I/O module installation
and connection.