MOD 30ML Multiloop Controller
MODULAR I/O CONNECTIONS
4.3.7 2020N Remote I/O Interface Module (RIO) (discontinued)
Make remote I/O interface connections as shown in Figure 4-9. One remote I/O interface
module is required for each remote I/O network. The remote I/O interface module is scanned
every 50ms by the controller. A maximum of 2 RIO modules are allowed per instrument.
Specifications are:
REMOTE I/O INTERFACE RS485 SERIAL NETWORK
Bus Master
2020N Remote I/O Interface Module (end of bus)
Bus Slaves
Remote I/O Digital Modules
Maximum Length
500 meters (1600 feet)
Baud rate
187.5K
Max addresses
32 (31 slaves + 1 RIO master at address 0)
Termination
120 ohm resister is required across the two conductors
at the end of the cable (2 shipped with RIO module)
Shield
Required over 50 meters (160 feet)
REMOTE I/O INTERFACE CABLE
Indoor use
Belden #9182
Indoor plenum use
Belden #89182
Underground use
Belden #9815 twisted twinax
Outdoors above ground use
NOT recommended
Wiring
Use same cable type throughout network. Avoid
interruptions (wire to same terminals if necessary).
Do not wire through terminal blocks.
Table 4-3. Supported Remote I/O Modules (discontinued)
Module Description
Digital Input Modules .....................ICSI 08 D1 8 non-isolated 24VDC input channels
ICSI 08 E1 8 isolated 24VDC input channels
ICSI 08 E3 8 isolated 120VAC input channels
ICSI 16 D1 16 non-isolated 24VDC input channels
ICSI 16 E1 16 isolated 24VDC input channels
Digital Output Modules ..................ICSO 08 R1 8 relay output channels 2A
ICSO 08 Y1 8 transistor output channels 24VDC 2A
Digital Input/Output Modules ........ICSK 20 F1 12 non-isolated 24VDC input channels and 8 isolated
relay output channels
ICSC 08 L1 8 user-configurable channels for 24VDC input or
24VDC 500mA transistor output
* NOTE:
Modules are available in three forms: -120 for 110/120Vac external power, -230 for
220/230Vac external power and -24 for 24Vdc external power. All modules mount on a ECZ
remote I/O module carrier. See IB-23C601 for details on Remote I/O module installation
and connection.
64