Detroit Radiant Products Company HL3 Series User Manual

Page 17

Advertising
background image

17

HL3

Series

Check to make sure gas pressure is within minimum and

maximum inputs, as indicated on the heater’s rating plate.

Is gas pressure OK?

Were the gas lines purged of air?

Is the heater properly

grounded? Is the heater’s

polarity correct?

With microampmeter, check DC

amperage at flame rod. Is it

greater than 1.0 microamps?

Check to make sure flame

sensor wire is OK and then

replace circuit.

Sensing rod is faulty or flame is weak.

Check to make sure heater is operating

at proper gas pressure as indicated on the

heater’s rating plate and then, if needed,

replace sensing rod.

Replace gas valve.

Yes

Correct problem.

Correct problem.

No

No

Yes

Yes

No

Yes

Purge gas line.

No

4.0

Troubleshooting Guide

Is there 24V across the GROUND and HIGH

(HIGH to COM on heaters with optional

isolation relays) on the terminal strip located

on the outside of the control box?

Repair or replace faulty

wiring or thermostat.

Replace relay.

No

If heater does not go into high fire mode:

Measure voltage across the red wire

on the VALVE and GROUND (red wire

on RELAY to GROUND on heaters with

isolation relays). Is it 24V?

Yes

No

Yes

Replace gas valve.

NOTE: To confirm that the heater is not in high fire mode, check manifold pressure.

If manifold pressure is 3.3” to 3.5” for natural gas or 9” to 10” for propane, the light is faulty and should

be replaced.

When the heater is in low fire mode, manifold pressure is approximately 2.0” to 2.5” for natural gas or

5.0” to 6.5” for propane. If this is the case, the following troubleshooting steps should be followed:

Advertising