2.0
Installation
•
Heater Mounting
•
Optional Mounting Kit
Heater Mounting
The heater shall be mounted in a fixed position attached from a structure that can evenly support the total 
force and weight of the heater. The mounting means shall be independent of the gas and electrical supply 
line. All hangars and bracket material shall be of noncombustible construction. Examples of suitable 
material include, but are not limited to, Steel channel, steel tubing, threaded rod, or field fabricated 
hangers that are adequate to bear the load. In some cases, the heater may need to be isolated from 
vibration with the use of vibration isolating devices. 
The heater must be level from side to side and can be set at an angle between 0° and 30° from horizontal.
Figure 2.1
•
Heater Dimensions
Optional Mounting Kit
Optional adjustable mounting kits and brackets are available for the Patio Heater. Refer to the insert that 
was packaged with the mounting brackets for complete installation instructions.
WARNING
!
Improper suspension of the infrared heater may result in collapse and persons being 
crushed. Always suspend from a permanent part of the building structure that can support 
the total force and weight of the heater. 
Failure to maintain minimum clearance to combustibles may result in fire and/or explosion, 
property damage, serious injury or death. Always maintain minimum clearances and post 
signs or provided tags (F/N: LL01) where needed. Signs should state the hazards for the 
particular application and be legible for the building occupants. Consult the factory or a 
factory representative for additional information on signage compliance.
END VIEW
SIDE VIEW
2.75”
10.875”
9”
48.375”
9”