Warning – Detroit Radiant Products Company DSC Series User Manual
Page 16
 
16
DSC
Series
Leak Testing
Use a soap solution or equivalent for leak testing. Leak testing solution must be non-corrosive, and be 
rinsed off immediately after the leak test. Never test for leaks with an open flame. Failure to comply could 
result in personal injury, property damage or death.
Always leak test the final gas assembly for gas leaks according to the procedures outlined in NFPA 54 
and all local codes/or standards.
For leak testing on pressures below ½ PSI
Before leak testing, close the field installed manual shut off valve shown in Figures 2.4 and 2.5 (pg. 15) on 
the supply line to isolate the gas valve from the pressure. 
NOTE: All factory installed gas connections
have passed an approved leak test.
For leak testing on pressures above ½ PSI
When leak testing with pressures above ½ PSI (14 inches W.C.) the unit’s gas controls must be isolated 
from the supply pipe. Close the field installed manuals shut off valve, disconnect the supply line to the 
unit, and temporarily cap the supply line for testing purposes.
2.0
Installation
•
Gas Supply
•
Leak Testing
WARNING
!
!
Gas pressures to the appliance controls must never exceed 14 inches W.C. (1/2 PSI). 
Supply pressures greater than 14 inches W.C. can damage the controls, resulting in 
personal injury, property damage, or death.
WARNING
!
!
Testing for gas leaks with an open flame or other sources of ignition may lead to a fire or 
explosion and cause serious injury or death. Test in accordance with NFPA or local codes.
WARNING
!
!
Failure to install, operate or service this appliance in the approved manner may result in 
property damage, injury or death. This heater must be installed and serviced by trained gas 
installations and service personnel only.
The installation of this heater must conform with local building codes or, in the absence of 
such codes, the National Fuel Code (NFPA 54).