5 operation of mimic-panel leds, Single ups start sequence on normal ac input, Single ups start sequence on bypass ac input – APC GALAXY 5000 User Manual
Page 44: Io 3s, Operation
Advertising

34001813EN/AE
- Page 44
3. Operation
3.5 Operation of mimic-panel LEDs
Single UPS start sequence on Normal AC input
Single UPS start sequence on Bypass AC input
Steps
Action
LED (39)
LED (40)
LED (41)
LED (42)
LED (43)
1
Q1 open
Off
Off
Off
Off
Off
2
Close Q1
green
Off
red
Off
red
3
Close QF1
green
Off
Off
Off
red
4
Close Q4S
green
Off
Off
Off
green
5
Close Q5N
green
Off
Off
green
green
6
Open Q3BP
green
Off
Off
green
green
7
Press ON button (37)
green
green
Off
green
Off
Steps
Action
LED (39)
LED (40)
LED (41)
LED (42)
LED (43)
1
Q4S open
Off
Off
Off
Off
Off
2
Close Q4S
red
Off
red
Off
green
3
Close Q5N
red
Off
red
green
green
4
Open Q3BP
red
Off
red
green
green
5
Close Q1
green
Off
red
green
green
6
Close QF1
green
Off
Off
green
green
7
Press ON button (37)
green
green
Off
green
Off
I
O
3s
39
40
42
41
43
Advertising