External battery cabinet / auxiliary cabinet
Dimensions
UPS power
rating (kVA)
Dimensions
(H x W x D)
20/30/40/60
without battery
1900 x 712 x 850 mm
80/100/120
without battery
1900 x 712 x 850 mm
20/30/40/60/80
with internal
battery
1900 x 1112 x 850 mm
Weight in kg (UPS without battery or with
built-in battery)
Backup
time
UPS power rating (kVA)
20
30
40
60
80
100
120
Without
battery
400
400
400
520
520
5 min
808
808
958
1120
10 min
808
958
1045
15 min
958
1045
30 min
1045
Dimensions (H x W x D) and weight
Cabinet 700
mm (empty)
1900 x 712 x 850 mm
135 kg
Cabinet
1000 mm
wide
(empty)
1900 x 1012 x 850 mm
150 kg
Weight in kg (cabinet alone)
Backup
time
UPS power rating (kVA)
40
60
80
100
120
5 min
885
980
10 min
885
1142 1307
15 min
885
1142 1307 1764
30 min
882
1307 1764 2439 2742
Weights highlighted in grey are for double
cabinets.