OPERATION

4.4

Methods of Externally Triggering or Pacing A3, A7, and A8 Pumps

Switch or transistors must be capable of switching 24V DC at
15 milliamperes. Minimum time in low impedance state (ON) is
25 milliseconds. Minimum time in high impedance state (OFF)
is 50 milliseconds.

NOTE: Pins 1 (Brown wire) and 2 (White wire) must be connected/

shorted together in order for the pump to be ‘ON’ in external

mode.

4. Opto

Isolator

2. NPN Transistor

Base goes high

to trigger pump

White

3. PNP Transistor

Base goes low

to trigger pump

Method of Triggering A3, and A7 Pumps Through External Control Connector

1. Switch Closure

Switch closing

triggers pump

PIN

3
2

3

2

3

2

3

2

Blue

− White

+ Blue

− White

+ Blue

− White

+ Blue

Full (Open)

Empty (Closed)

4-20 milliamp DC

4-20 milliamp DC

Higher Frequency Pulses

Lower Frequency Pulses

Pulse

Transmitter

MICROPACE

4 DIGIT DIVIDER

MP-400D

MICROPACE

A/D CONVERTER

MP-100

MICROPACE

4 DIGIT MULTIPLIER

MP-500M

RFP Flowmeter

Programmable

Divider

Programmable

Divider

FC Flowmeter/Contactor

A3, A7, A8

A3, A7

A8

Optional

Low Level

Sensor

The default configuration

for the Remote On/Off
input is: open contacts

= pump stopped, closed

contacts = pump enabled.

Therefore pins 1 and 2
of the External Control

Connector must be shorted

together in external mode

for the pump to respond to

external signals.

These pumps have two operating modes: Local (Pulse Indicator Light flashes
green) and Remote (Pulse Indicator Light flashes yellow). Pressing the Power/
Mode Selection Button switches between Local and Remote modes. The default
configuration for operating mode is Local mode.

When the pump is in Local mode the Remote On/Off input is ignored. When the
pump is in Remote mode the Remote On/Off input is always monitored. The
pump will return to the last power mode if power is interrupted.