Pach and Company AeGIS 4000RT Manual User Manual

Page 15

Advertising
background image

Connect to Normally Closed (N.C) and COM if normally closed door strike is used. Door is closed if the strike is
energized and open if not energized

• 18-gauge 2-conductors stranded is recommended.

Step 7

AUXIN.

Radio Frequency Reader (ARFR) factory prewired.

Step 8

POWER.

ONLY use a Class 2 transformer rated 12 VAC 20VA (supplied) or 12 VDC 20 VA to power the AeGIS 4000RT.
Optional 12 VDC 4Ahr battery back up with built-in charger can be installed as shown in figure 2.2. The output volt-
age of the battery and charger must be between 13.5 VDC - 15 VDC, lower than 13.5 VDC will cause the on
board relay not working properly and higher than 15 VDC will damage the system.
Warning:
Do not use 12 VAC 20VA (supplied), if battery back up is used, to do so may damage the system or
cause injury.

Figure 2.2 Battery Backup Connection with Built-in Charger

Pach and Company

Page 7

AeGIS 4000RT

Chapter 2. Installation