PINKERTON Installer Manual

Name of
option

Address


Value allowed


Option Description

Dialler options

170

Select
1, 2, 6, 7, 8

1 Rotary

Dial.

The system is factory programmed for tone dialling. Select
this option to enable rotary (decadic) dialling.

2 Open

after

alarm.

When this option is selected, the system will send an
opening report only if Zone alarms have occurred during
the last armed period. This reduces the number of
telephone calls made but allows the central station to be
informed when an authorised access is taking place after
an alarm has occurred.
To use the open after Zone alarm facility:
Enable Open After Alarm at address 170, option 2.
Disable all options at address 064 except for option 8.
Note that when the Open After Alarm option is set, the
central station will never receive a closing report.

3 not

used

4 not

used

5 not

used

6 Send Zone ID (Personal dialling)

Option ON: The called phone hears a number of beeps
equal to the Zone number which triggered the alarm.

Option OFF: The called phone hears a high/low siren
tone.

7 Send

restoral

reports

When selected, the system will send a restoral report to
the monitoring station when the alarmed input has
resealed.

8 Send isolated Zone reports

When selected, the system will send isolated Zone reports
to the monitoring station along with the closing report
when the system is turned on.

Dialler format

174

Select 0, 1, 3, 4

0 Disables dialler (handy installer option for temporary or

permanent disabling of dialler)

1 Ademco high speed with checksum
2 not

used

3 Contact

ID

4 Personal

dialling

Maximum
dialling
attempts

175

00 - 10
attempts

Sets the maximum number of attempts the dialler will make
when triggered. Factory default is 6 attempts. Do not set to
over 10 attempts.