Modbus to bacnet pre-loaded gateway points – Fulton Caliber (CAL) SOLA Gateways User Manual

Page 22

Advertising
background image

__________________________________________________________

_____________________________________________________________________________________

Questions? Call (315) 298-5121 or visit us online at

www.fulton.com

©The Fulton Companies 2013
Supplement SOLA-IOM-2013-0220


2

Auto baud rates are only supported on BACnet MSTP

Return to Table of Contents

Modbus to Bacnet Pre-Loaded Gateway Points

Sola LEAD/LAG Bacnet points as of 12/5/12 V1.00

[Read points] (* points exclusive to lead lag)

1. *Lead lag master status [LLMstrStat] 0160

a. 0=Unknown