Note: If a Proto node Gateway is being used, it was fully programmed at the Fulton Factory and
should not require any changes on the Sola side. The customer connection side of the gateway may
require dip switch changes for baud rate and the required address. See the end of these instructions
for information on customer gateway setup.

1. From the Home Screen press Setup
2. Then Press Display setup
3. Then press tab Com 2

-

Check the Enable box

-

Choose baud rate if known or if a Proto Node Gateway is being used it should be 19,200

-

Press the save button

4. Then press the Gateway tab

-

Check Enable Modbus gateway

-

Press Gateway on COM2 Port

-

Press Save

5. Press the upper right Arrow to back out
6. Press Control Setup
7. Press Change Address
8. Password "sola" is required

-

Change the address to the required address

o If Protonode is used, Com 1 will be preset to address 2 on all boilers.

Note: The address in Yellow will say Com 1, Com 1 is an actual pass through of the
communication when a BMS is communicating directly to Com 2 through Modbus or a
Gateway. Any communication will "piggy back" on all the standard communication from
the display to the Sola base. Changing this address will not affect the communication
between the Display and the Sola.

9. Back out to the Home Screen and press the Sola

-

Press Configure

-

Press System Identification and Access

o When you change the above Com address the Sola will change the MB1 and

MB2 address. If boilers are being daisy-chained together through MB1 the
address will need to be changed back to what it was. For example: If the BMS is
communicating with is the Master boiler, MB1 should be 1, the next boiler MB1
would be 2 and so on up to 8 boilers.

Return to Table of Contents