USER PARAMETERS

*Refer to the "PARAMETER ACCESS & ADJUSTMENT" section on page 5.

Label

Name

Refrigerator Setting

Factory Preset

Freezer Setting

Factory Preset

Unit

Minimum

Maximum

Measure Input Configuration Parameters

CA1

Cabinet probe offset

0

-1

°F

-25

25

This parameter can be used to calibrate the digital display.

P2

Celsius/Fahrenheit

°F

°F

-

°C (0)

°F (1)

This parameter is used to change the temperature scale.

Main Regulator Parameters

r4

ENERGY SAVING setpoint (relative)

2

4

°F

0

99

This parameter is used to set the increase in setpoint when in ENERGY SAVING mode. See also "i10" parameter on next page.

r5

Overcooling setpoint

5

10

°F

0

99

This parameter is used to set the decrease in setpoint for "SUPER COOL MODE".

r6

Overcooling timeout

30

30

min

0

240

This parameter is used to set the length of time for "SUPER COOL MODE".

Compressor Protection Parameters

C6

Setpoint alarm COH

127

119

°F

0

199

This parameter is used to set the temperature of the COH alarm.

Defrost Parameters

d0

Defrost Interval

12

8

h

0

99

This parameter is used to set the defrost interval.

d8

Kind of Defrost Interval

(0) Time

(0) Time

-

(0) Time

(4) Calendar

This parameter is used to set the type of defrost interval. If real time defrost interval is required, set this to: (4) Calendar. The Hd parameters must be set to
the time defrosts are required.

d20

Max Time for Safety Defrost in Normal
Operation

N/A

120

-

0

500

This parameter is used to set the time if the compressor runs constantly so that a defrost will initiate.

Temperature Alarms Parameters

A1

Threshold minimum temperature alarm

30

-15

°F

-99

99

This parameter is used to set the threshold for the low temperature alarm.

A4

Threshold maximum temperature alarm

50

32

°F

-99

99

This parameter is used to set the threshold for the high temperature alarm.

A7

Alarm Delay

15

15

min

0

240

This parameter is used to set a time delay for the high and low temperature alarms.

A8

End of Defrost Time Delay

-

30

min

0

240

This parameter is used to set a time delay for the high and low temperature alarms after defrost terminates.

Evaporator Fan(s) Parameters

F0

Fans activity during normal operation

(4)THERMO_IF_CMP_ON

N/A

°F

(0) OFF

(5) rhL_rhH

This parameter is used to set the fan speed of the refrigerator evaporator fan(s) in the off cycle of the compressor. The factory preset is to run the fans at low
speed during the off-cycle. To set to high speed in the off-cycle, set this parameter to (1) ON

Digital Inputs Parameters

i2

Door Alarm Delay

5

5

min

-1

120

This parameter is used to set the time length of door opening that will trigger an "id" alarm (door ajar).

*Parameters Table continued on next page