Provider series - emergency lighting, Unit testing, Maintenance – Emergi-Lite Provider PRO-2N/PRO-3N Series User Manual

Page 2

Advertising
background image

Provider Series - Emergency lighting

Emergi-Lite

Tel: (888) 552-6467

Fax: (800) 316-4515

www.emergi-lite.com

02/14 750.1705 Rev. C

2/2

d. Line cord installation (option)

Mount the backplate to the wall. Install the strain relief (see fig. 3b). Using
pliers, crimp strain relief onto the line cord. Keeping pressure on the pliers,
insert the strain relief into the pre-drilled hole on the housing.

7. Make the proper connections. The system can accept input voltages of 120/

277 VAC (see fig. 4).
120 VAC — Connect the black (120 VAC) and white (neutral) leads to the
building utility. Insulate the unused wire.
120 VAC with line cord (optional) — Before making the connections, fol-
low the line cord installation instruction in section 6e. Make the proper con-
nections. Connect the wire with the smooth side from the line cord to the
black (120 VAC) on the unit and the ridged wire from the line cord to the
white (neutral) on the unit. Insulate the unused wire. Connect the green wire
on the transformer (if applicable) or insulate the unused green wire from the
line cord.
277 VAC — Connect the orange (277 VAC) and white (neutral) leads to the
building utility. Insulate the black wire.

Route entry wires to avoid contact with the transformer, battery terminals
and charger PCBA. Refer to figure 4.

8. Connecting external lamps: pass external DC wires into the unit and connect

to internal lamp wires or directly to the PCBA depending on the model.

9. When ready to energize AC circuit, connect the battery.
10. Slide the housing over the tabs; conduit side on housing over conduit side

on backplate (see fig. 5). Assemble the conduit side first, then align the tabs
on the other side of the housing and of the backplate. Press together until it
snaps.

11. Remove the clear lens by prying with a screwdriver, where indicated (see fig.

2).

12. Rotate heads to desired position and replace clear lens.
13. Energize AC. The AC pilot indicator, located under the cover, will illuminate

(see fig. 5).

Vandal resistant (option)

Units with vandal resistant option: there are three vandal resistant screws. Two
are securing the cover, and the other one secures the housing and the backplate
(see fig. 6).

Unit testing

Manual testing

Press test switch (see fig. 5). The emergency lamps will illuminate. When switch
is released, lamps will go off. Allow unit to charge for 24 hours before initial test-
ing.

Automatic testing and diagnostics

The automatic testing and diagnostic function includes a micro-controller which
self-tests the unit on a monthly basis and identifies as well displays failures of
the electrical components: battery, battery charger, lamps.

Self-test
The self-test is performed every month for 1 minute, every 6 months for 30
minutes, and annually for 90 minutes.
Diagnostic function
–For diagnostic function, refer to “User Manual for AD”
–For Nexus models, refer to “Nexus addendum”

Maintenance

None required.
If AC supply to the unit is to be disconnected for 2 months or more, the battery
must be disconnected.

Conduit hole
to knock out

Figure 3d

DC wires

AC wires

White neutral

Black 120 VAC

Figure 3

Orange 277 VAC

Housing

PCB

Transformer

Unused primary wire must be insulated to prevent shorting.

Make all AC connections

on this side of battery

Battery

Figure 5

Assemble conduit
side first

Test switch

AC pilot indicator

Close housing until it snaps

Figure 6

Vandal resistant
screws for
vandal resistant
option

Important: all AC or DC connections must be done in
individual external junction boxes.