Hzm series, Heater and thermostat control (option), Testing – Emergi-Lite HZM Series User Manual

Page 2: Maintenance, Diagnostics

Advertising
background image

HZM Series

2/2

Emergi-Lite

Tel: (888) 552-6467 ext. 547 or 255

Fax: (888) 867-1565

www.emergi-lite.com

03/11 750.0299 Rev. C

8. When ready to energize AC, connect batteries by plugging the red

leads into the positive terminals and the blue leads into the negative
terminals. Lamps will not light at this time.

9. Energize AC. Allow unit to charge for 24 hours before initial testing.

Heater and thermostat control (option)

This option is used in areas where temperature may drop below 0°C.
The thermostat will activate the heating pad at 0°C and will cut at 16°C.
The heating pad is rated at 50 watts. Contact factory for temperature lim-
itations.

Testing

To test: depress test switch, DC lamps will illuminate. Release switch and
DC lamps will extinguish.

Maintenance

None required. Unit should be tested in accordance with local codes and
Life Safety Code, NFPA101. This equipment is furnished with a low bat-
tery disconnect circuit in the emergency mode. However, if the AC supply
to the unit is to be disconnected for 2 months or more, the battery must
be disconnected. Do not allow battery wires to short circuit.

Diagnostics

*Note 1 — Battery failure when the battery voltage is below 80% of nom-
inal 6V or 12V.
Note 2 — This feature is not a complete self-test / self diagnostic circuit
as described by UL924.

STATUS

BATTERY

FAULT

LOAD

FAULT

PILOT

LIGHT

Normal

Off

Off

On

Battery Disconnect

On

Off

Flash

* Battery Failure

On

Off

Flash

Load Disconnect

Off

On

Flash

Overload

Off

On

Flash

Batt <Fault> Load

Pilot Light

Test