Self-powered models, Caution, Maintenance – Emergi-Lite Prestige DX Series User Manual

Page 3

Advertising
background image

Prestige DX & DXN - Die Cast Aluminum LED Exit Series

Emergi-Lite

Tel: (888) 552-6467 ext. 547 or 255

Fax: (888) 867-1565

www.emergi-lite.com

04/07 750.0895 Rev.C

3/3

Self-Powered Models

Manual testing

Press test switch. Legend will flicker, but remain lit, AC pilot lamp will
extinguish. On release, pilot lamp will illuminate, and automatic charger
will restore battery to full charge.

Automatic testing and diagnostic

All models have automatic testing and diagnostics which includes a
micro-controller that exercises, self-tests, the unit on a monthly basis and
identifies and displays failures of the electrical components: battery, bat-
tery charger, lamps, LEDs.
Self-test
The self-test is performed every 30 days for 30 seconds, every 60 days
for 30 minutes, and annually for 90 minutes.
Diagnostic function
The diagnostic function uses three red LED indicators: one external,
near AC pilot lamp, and two internal, inside the unit. The unit has to be
opened to read the status of the internal indicators.
External: Service Required. Blinks if any alarm condition is detected
(See fig. 8).
Internal: Battery Alarm, Charger Alarm. Steady ON if alarm condition
exists (See fig. 9).
Normal operation, No fault — Service Alarm is OFF and one of the two
internal LED blinks, showing that the micro controller is active.
Faulty operation — Service Alarm blinks.
Battery Alarm ON, Charger Alarm OFF: Check battery or replace battery.
Battery Alarm ON, Charger Alarm ON: Check LED strip.
Battery Alarm OFF, Charger Alarm ON: Check charger circuit.
Nexus models
Nexus models use two local indicators. One is a green LED for AC pilot
lamp. The other is a tricolor LED (Service) which identifies and displays
the Nexus status. The table below describes each status:
Nexus Tricolor LED — Status table

Caution

This unit is an integral component of a remotely monitored and
controlled self-test/self-diagnostic emergency lighting system. In
the event that control is suspended or becomes inoperable, this
unit may have to be manually tested as required by local code regu-
lations.

Maintenance

None required. If AC supply to the unit is to be disconnected for 2
months or more, the battery must be disconnected, Self-Powered Mod-
els only.
Note — Nickel Cadmium battery units are shipped discharged and may
require 10 minutes of connection to AC supply before start-up test proce-
dure, and 96 hours to reach full charge or 24 hours to reach a 30 minute
discharge.

Canopy

Figure 7

LED Strip

Nexus data cables

Black (120)

Orange (insulate)

White (neutral)

Black (insulate)

White (neutral)

Orange (277)

120 VAC or 277 VAC

Sign

30 mm

Interface

Data

Tape

Nexus data cables

Nexus data

Nexus

Transformer

Nexus model wiring

terminal block

Figure 8

Service

Figure 9

Charger alarm

Battery Alarm

Diagnostic circuit board

Uncommissioned

Commissioned

Normal

Red/Off pulsing

Green steady

Under test

N/A

Green/Off pulsing

Wink mode

Yellow-orange/(red or off) pulsing

Yellow-orange/Off pulsing

Neuron faulty

Red Steady

Red steady

Power fail

Off

Off

Battery disconnected

N/A

Off