Premier series - thermoplastic led exit sign, Ac/dc models, Self-powered models – Emergi-Lite Premier Series - Exit Sign User Manual

Page 2: Maintenance

Advertising
background image

Premier Series - Thermoplastic LED Exit Sign

Emergi-Lite

Tel: (888) 552-6467

Fax: (800) 316-4515

www.emergi-lite.com

11/09 750.1372 Rev. B

2/2

canopy lock to canopy. However, for applications having a greater
risk of exposure to abnormal impacts, we suggest to always use the
canopy housing screw(11) (fig. 1 and 3). Make the proper wire con-
nections. The “Quick-install” canopy is equipped with ribs allowing
you to hang the unit on the spider plate to facilitate wiring (See fig.4).
Feed the excess wire into the junction box. Unhook unit and slide ribs
on canopy into designated notches on the spider plate (See fig. 4).
Secure the canopy to the junction box using the canopy screw(s) pro-
vided(10).

6. Remove the appropriate chevron(s) on the exit door by holding sign with

both hands. Push chevrons from the inside with thumb (See Fig. 5). You
may need to unsnap the diffuser panel to do so.

7. Connect the battery.

8. Reinstall exit door(s).

9. Energize AC. Sign will illuminate.

AC/DC Models

Refer to Fig. 6 for AC & DC wiring.

For DC portion — Wire the Red lead (+) to the positive DC input voltage
and the Blue Lead (-) to the negative DC input voltage. Note: DC input volt-
age range is 6 volts to 48 volts.

Self-Powered Models

Manual testing

Press test switch. Legend will flicker, but remain lit. On release, external
green LED will illuminate, and automatic charger will restore battery to full
charge.

Automatic testing and diagnostics, optional

The models with the automatic testing and diagnostic option include a micro-
controller which self-tests the unit on a monthly basis and identifies as well
displays failures of the electrical components: battery, battery charger,
lamps, LEDs.

Self-test
The self-test is performed every 30 days for 1 minute, every 6 months for
30 minutes, and annually for 90 minutes.

Diagnostic function
The diagnostic function uses an external green LED indicator. Service is
required if the green LED blinks indicating that an alarm condition is
detected ( See Fig. 7).

Maintenance

None required. If AC supply to the unit is to be disconnected for 2 months or
more, the battery must be disconnected, Self-Powered Models only.

Note — NiCd (Nickel Cadmium) batteries are shipped discharged and may
require 10 minutes of connection to AC supply before start-up test proce-
dure, and 96 hours to reach full charge.

o

Green

Steady On

AC On

-o

Green

One Blink

In Test

o

Red

Steady On

Battery Disconnect

-o

Red

One Blink

Battery Failure

o-o

Red

Two Blinks

Charger Failure

o-o-o-o

Red

Four Blinks

LED Strip Failure

Figure 4

NOTCHES TO RECEIVE
RIBS ON CANOPY

Figure 6

(self-powered

DC wires for

remote DC supply

models only)

Battery

Transformer

Canopy

Ground

120 VAC Black

White Neutral

Red + DC

Blue - DC

LED Strip

through loop.

(Back mount only)

Pass wires

277 VAC Orange

around snap.

only)

(Side mount

Wrap wires

or from battery

Figure 7

External

-for self-powered models only

green LED

Test switch

Figure 5