Retract-lite: dc-remote lighting fixture – Emergi-Lite Revelation Remote Fixture Series User Manual

Page 2

Advertising
background image

Retract-Lite: DC-Remote Lighting Fixture

2/3

Emergi-Lite

Tel: (888) 552-6467 ext. 547 or 255

Fax: (888) 867-1565

www.emergi-lite.com

08/07 750.1297 Rev. A

“U” Bracket Installation in a T-bar Ceiling (Figures 3, 4 and 5)

The DC-remote fixture unit includes as an option (specify when order-
ing) a hardware kit for installation in T-bar ceiling structures.

1. Remove the four screws installed in the pem-studs of the “U” bracket

and replace them with the longer, 1-inch screws provided in the hard-
ware kit. Turn them two - three threades in the pem-studs.

2. Mount the adjustment brackets from the hardware kit on the two

sides of the “U” bracket, using the studs and nuts. Do not tighten (see
Figure 3).

3. Slide hanger bars through the tabs in the adjustment brackets. If

needed, bend the middle tab of the adjustment brackets over the
hanger bars (see Figure 4). Align the “U” bracket as required and fix
location by cutting a hole in the ceiling panel of the size of the “U”
bracket (8-1/4 inch by 5-3/4 inch).

4. Rest the assembly on top of grid members. The notch on bars

should hook over grid member (see Figure 5). Place the “U” bracket
with its flange sit on the panel and tighten the nuts on the studs of the
side brackets (see Figure 4). If required by code, hang the whole
assembly from the framing above ceiling grid with solid wires, (pro-
vided by others).

5. Pass the electrical cable out through the hole.

Figure 5

Figure 2c

Figure 3

Figure 4

Studs

Middle tab
to bend

Notch