9.8

Power voltage / Inside Power Supply

9.8.1 code 7-0 power voltage error / inside power supply abnormal

The controller internal power supply circuit is not working properly.

This abnormal is caused from only 3 items.
1. The controller internal power supply has failed
2. If the environment temperature is more than 113 degrees Fahrenheit ( 45 degree
centigrade ) without any air flow.
3. Source voltage is very close to the limit (253 volts ac) and the environment temperature is
also close to the limit.

RECOVERY:
1. Replace the controller
2. Provide additional cooling to the enclosure.
3. Verify and correct the source voltage as required.