FIREPOWER XLSV User Manual

Page 2

Advertising
background image

Remote paging can be provided from any telephone zone

(Warden's Page) with selection at the command console.

In addition, specific telephone zones can be pre-selected

as automatic page zones on a selective or All Call basis.

Speaker zones are selectable for either 25 Volt or 70.7 Volt

operation and either Style Y (Class B) or Style Z (Class A)

wiring configuration. Strobe circuits may also be wired as

Style Y or Style Z.

Speaker, Strobe and Firefighter's Telephone zones can be

provided as either modules or plug-in type cards, installed

in the main enclosure or remote voice system transpon-

ders. The cards are plugged into the standard XLS CC-5/

CC-2 card cages. The XLS Control Point Module HCP can

also be used to provide a remote telephone zone, speaker

zone or notification appliance circuit.

SCM-8 Switch Control Module
The SCM-8 is a FireFinder XLS option module which

provides manual control of the Emergency Voice Evacua-

tion System or manual fire system control. Each SCM-8

module provides eight momentary pushbutton switches

and 16 LED's to indicate their status. Each switch is

assigned two LED's and a label to indicate the switch's

programmed usage. The label slides behind a clear

protective membrane. One of the LED's assigned to each

switch is a dual color LED used to indicate what type of

signal is active.

Each SCM-8 and each switch is fully programmable and

may be used to control speaker circuits, and a wide range

of general system functions such as All Call, All Evac,

Warden's Page, Speaker, etc. Any number of circuits may

be grouped and controlled by a single switch. Switch

usage and zone groupings are assigned using the ZEUS

system programming software.The SCM-8s are mounted

on a hinged panel as a partof the FireFinder XLS Command

Console enclosure.

SCM-8

LCM-8

FCM-6

LCM-8 LED Control Module
The LCM-8 is an FireFinder XLS option module which

provides LED annunciation of system activity. Each LCM-

8 module contains eight groups of 2 LED's, each of which

can be assigned to desired outputs using the ZEUS

programming software. Eight LED's are dual color capable

of being lighted either RED or GREEN flashing or steady.

The remaining LED's are AMBER flashing or steady. A

space is provided for labeling of LED functions. The label

slides behind a clear protective membrane. The LCM-8

dimensions are identical to the SCM-8 and is mounted on

the same hinged panel as a part of the FireFinder XLS

Command Console enclosure.

FCM-6 Fan, Motor, dampers Control Module
The FCM-6 is an FireFinder XLS command console option

module that provides manual control of building HVAC

system fans, motors, and dampers. EachFCM-6 module

provides (6) sets of (3) push button switches for manual

system control. Each switch has 3 associated LEDs to

indicate Fan/Damper/Motor status: OFF (Red LED), ON

(Green LED), TROUBLE(Yellow LED).