background image

at 25VRMS, 180 watts of audio at 70VRMS or 165 watts of

audio at 100 VRMS. It mounts in one module space on the

CAB-MP mounting plate. The ZAM-180 is capable of

amplifying any one of the 8 digital audio channels that are

transmitted from the DAC-NET (Digital Audio Card) via the

digital audio bus ASI (Audio Serial Interface). The ZAM-180

amplifier is supervised for functionality.

The ZAM-180 can be used as a single 180 Watt speaker

zone for one to eight channel applications or as a bulk

amplifier for one or two channel applications feeding high

level audio to the ZIC-4A or ZIC-8B.

FMT Fireman's Master Telephone
The FMT provides firefighters with an emergency tele-

phone system for communication with remote locations.

The FMT mounts to the rear of the Inner Door of a CAB1,

CAB2, CAB3, or REMBOX4 Enclosure. It includes a

handset for the operator of the telephone system.

The XLSV firefighter's telephone unit is designed for

maximum performance in communication. The FMT

circuitry allows the master telephone and at least 5

telephone stations to be off hook simultaneously with no

degradation of audio quality.

The FMT also supports Warden Page function which allows

live voice announcements from any remote telephone.

Telephone zone call-ins are annunciated on the appropriate

SCM-8 switch module. Remote stations receive an

acknowledge tone when dialing into the command center

prior to the call being answered indicating a call-in in

progress and a busy tone if calling into the command

center and another telephone zone is already on line.

Diagnostic LEDs are located on the back of the FMT to

indicate power is applied to the module and failure of the

card, CAN communication or phone.

FMT

TZC-8B Firefighter's Telephone Zone Card
The TZC-8B provides a way for emergency response

personnel located throughout a building to speak to one

another during emergency situations.

The TZC-8B is an XLSV option module which plugs into a

CC-2 or CC-5 card cage providing 8 firefighters telephone

zones. The zones have an off-hook acknowledge tone as

well as a Command Console busy tone.

Each telephone zone uses a single pair of wires and is

individually supervised in a Class B type mode. Field

wires are connected to one or more phone jacks or sta-

tions.

Zones are also individually power limited per NEC 760.

Each zone also contains transient protection.

Up to 5 telephone stations may be off-hook simulta-

neously in a party line mode with no loss of audio quality.

HCP
The HCP provides an intelligent control point for the

FireFinder XLS Control Panel. The HCP can be

programmed as an independent, remotely located tele-

phone zone, speaker zone or notification appliance circuit.

The HCP is designed to be used with the Siemens Fire

Safety notification appliance product line. The HCP commu-

nicates through the DLC analog loop and can be wired

either Class A (Style Z) or Class B (Style Y).The 24 VDC

power input comes from either the control panel or from

any UL listed power limited, auxiliary power supply.

TZC-8B

HCP