System Operation

151209

8-7

8.5.9

Silence alarms or troubles

Press

and enter your code or rotate the key at the prompt. If an external silence

switch has been installed, activating the switch will silence alarms or troubles. If you are
already using system menus when you press

, you will not need to enter your code or

rotate the key.

Note: Alarm and trouble signals that have been silenced but the detector remains un-restored will un-silence ev-

ery 24 hours until it is restored.

8.5.10 Reset alarms

Press

and enter your code or rotate the key at the prompt. If an external reset switch

has been installed, activating the switch will reset alarms. If you are already using system
menus when you press

, you will not need to enter your code or rotate the key.

8.5.11 Check Detector Through Point Status

The control panel constantly monitors smoke detectors to ensure that sensitivity levels are in
compliance with NFPA 72.

If sensitivity for a detector is not in compliance, the panel goes into trouble, generating a CAL
TRBLE condition. A detector enters a CAL MAINT state to indicate that it is approaching an
out of compliance condition (but is currently still in compliance).

When a CAL TRBLE condition occurs, the central station receives a detector trouble report
(“373” + Zone # for Contact ID format; “FT” + Zone # in SIA format).

To check sensitivity for an individual detector, follow the steps below. Section 8.5.17 provides
instructions for printing the status of all detectors in the system.

1. From the Main Menu, press for Point Functions.

2. Press for Point Status.

3. Select the module where the point you want to check is located.

4. Enter the number of the point you want to check and press

.

SILENCE

SILENCE

RESET

RESET

2

2

ENTER

Advertising