BTR TANK TYPE HEATERS

SERVICE HANDBOOK

A.O. Smith Water Products

Service Handbook

Irving, Texas ©2000

Training Department

20

STEP 2

HIGH LIMIT, LEFT TERMINAL TEST

STEP 2. HIGH LIMIT, LEFT TERMINAL TEST. Test for 24 VAC between the left high
limit terminal and ground.

IF

THEN

The meter does not read 24 VAC:

• Check wiring between transformer and

high limit.

The meter reads 24 VAC:

• Go to Step 3.

Note: The high limit (Energy Cut Off) opens if the tank water temperature exceeds 205
degrees.

The control is resettable (manually) when the tank water temperature drops

below 185 degrees.