Section 3: Installing the Instrument and Plug-In Cards

10/08 25

51207 Revision 1

3.4.2 Cable Connection in the D-Sub Connector Mating Plug


The connections on the back panel are plug-in type. Keep the conductors as short as possible and
connect them to the terminals. The connector housings are conductive (metallized), i.e., part of the
shield, and must be fastened to the back panel by screws.

Mounting a cable:

•

Open the connector housing (catches)

•

Release and open the cable clamp

•

Remove approx. 50-60 mm of the cable insulation

•

Shorten the shield to 5 mm and bend it over the cable

sheath

•

Remove 3mm wire insulation and connect it by soldering

•

Insert the pin unit

•

Put the cable under the cable clamp

The grounding tongue presses on the shield bent
backwards; the clamp presses on the cable sheath

•

Close and tighten the cable clamp

•

Check the strain relief

•

Insert the mounting screws on both sides

•

Close the connector housing (catches)


The shields must be connected to the metal housings on
both ends of the cable.