Material Prepare for Installation

Typical Wiring block diagram of the Power Inverter:











12V Battery Bank:

The use of deep cycle battery is highly recommended for power inverter application

For battery size, you need to identify how much you will be using them between charges.
KISAE do recommends you purchase as much battery capacity as possible. See more on
Battery Run time and Load in Section 4.

Fuse or Circuit Breaker:

DC-rated fuse or DC-rated circuit breaker connected along the DC positive line is required.

For MW 1210, SW 1210, select a fuse or circuit breaker with a minimum of 150 Adc

For MW 1215, select a fuse or circuit breaker with a minimum of 225 Adc

For SW 1220, select a fuse or circuit breaker with a minimum of 300 Adc

Based on the size of the battery bank chosen on the 12V Battery Bank above, determine the
overall short circuit current rating of the battery bank from the battery manufacturer. The fuse
or circuit breaker chosen has to be able to withstand the short circuit current that may be
generated by the battery bank.

Disconnect Switch:

Select a Disconnect Switch with the same or higher the rating of the selected fuse or circuit
breaker from the above.

The Disconnect Switch is used to disconnect the DC power between the power inverter and
the battery bank during service, maintenance or trouble shooting.


DC Input and Grounding Cable:

Use of low resistance wire is required for all the DC connections between the inverter and the
battery bank.

For MW 1210, SW 1210, uses minimum #2 AWG wire with maximum cable length of 5 feet.

For MW 1215, use minimum #1/0 AWG wire with maximum cable length of 5 feet.

For SW 1215, use minimum #2/0 AWG wire with maximum cable length of 5 feet.

Important: The unit is grounded through the ground stud of the unit located near the DC Input

Fan

opening




DC Input Terminals


Ground Terminal

Power Inverter

(MW 1210,

MW 1215,

SW1210,

SW 1220)

Disconnect

Switch

Fuse or Circuit

Breaker



12 V Battery Bank

(Charger system
sold separately is
required to charge
the battery bank
when battery is
discharged)

Pos +

Neg -

AC

&

USB

LOADS

Advertising