For the grounding cable connected between the power inverter chassis to the earth ground,
use a matching cable size as used on the DC Input Cable section.

Installing the Power Inverter System
WARNING

:

Electrical Shock Hazard

The unit ‘On/Off’ switch does not disconnect the DC power from the battery. Use the DC
Disconnect Switch or disconnect the DC input cables connection to disconnect the DC
power from the battery before working on any circuits connected to the unit. Failure to
follow these instructions can result in death or serious injury.

Power Inverter Installation:

Choose an appropriate mounting location.

For indoor use, the orientation of the unit can be mounted in any direction except with the DC
Input panel facing downwards.

For RV installation, the unit has to be mounted flat on horizontal surface.

Use mounting template below to mark the positions of the mounting screws.

Drill the 4 mounting holes and place the inverter in position and fasten the inverter to the
mounting surface.


Power Inverter Chassis Grounding Connection:

DANGER:

The Power Inverter has chassis to be grounded properly. Never operate the

Power Inverter without properly grounded. Failure to do so will result in death or serious
injury.

Connect the grounding cable’s ring terminal to the unit ground screw.

MW1215 15.0“

MW1210 12.3”

6

.9

SW1210 12.6”

SW1220 16.3”

MW1210 12.3”

MW1215 15.0”

SW1220 16.3”

SW1210 12.6

6

.9

SW

1220

6.

9”

SW

1210

9.

1”

SW

1210

6.

9”

SW

1220

9.

1”

SW1220