Feature setting – KISAE IC122055 Inverter-Charger 2000W User Manual

Page 10

Advertising
background image

 

 

 

Page 10

 

E02

Input battery voltage is too high and
unit has shutdown

Check battery voltage or determine if
any external charger is connected to the
battery bank

E03

AC output is overloaded or short
circuited and unit has shutdown

Check load connected to the output.
Reduce load and restart the unit

E04

Internal temperature is too high and
unit has shutdown

Turn unit off and wait for 15 minutes
before restarting. Check if any object
has blocked the air flow of the unit

E05

Input battery voltage is low and
warning occurs

Recharge battery as unit will shutdown
shortly

E06

AC output has sensed high and is
close to shutdown limit

Reduce load

E07

Internal temperature is high and is
close to shutdown limit

Reduce load and check if any ventilation
of the unit is blocked

E08 Not

used

E09 Not

used

E10

Battery Charging voltage too high

Check battery setting

E11

Battery bad

Battery did not accept charge

E12

Internal transfer switch temperature
is high and shutdown occurs

Reduce load and check if any ventilation
of the unit is blocked


AC Load on Inverter
Although the Power Inverter can provide high surge power up to two times the rated output power,
some high surge loads like sump-pumps, heavy duty motors etc. may still trigger the inverter
protection system even though the load falls within the power rating of the inverter. A higher power
Inverter-Charger is required for these appliances.

Estimate Run time on Load
Following run times are estimates for reference, based on using different battery bank sizes.
Actual run times may vary.

Estimate run time on different 12V Battery Bank Size

AC Load

60AH 120AH 180AH 240AH 300AH

50 W

11 hrs.

22 hrs.

33 hrs.

44 hrs.

55 hrs.

100 W

5 hrs.

11.5 hrs.

17 hrs.

23 hrs.

29 hrs.

200 W

2.5 hrs.

5 hrs.

8 hrs.

11 hrs.

13.5 hrs.

500 W

49 mins

2 hrs.

3 hrs.

4 hrs.

5 hrs.

1000 W

15 mins

49 mins

1.5 hrs.

2 hrs.

2.5 hrs.

1500 W

8 mins

27 mins

49 mins

1 hr

1.5 hrs

2000 W

N.R.

15 mins

34 mins

49 mins

1 hrs

2500 W

N.R.

11 mins

25 mins

37 mins

49 mins

3000 W

N.R.

N.R.

17 mins

27 mins

37 mins

Note: N.R. - Not Recommended

5. FEATURE

SETTING

To understand more about the unit features, read the following section and follow the instructions
to make changes to the desired setting.

Default Factory Setting:

In (Inverter): In1- inverter enabled in standby mode with load sense off
Cu (Charger): 40A or 55A – charger enabled (40A for IC121040 and 55A for IC122055)
AL (Alarm): AL1 – alarm enabled
Sd (UV shutdown): SdL – Under voltage shutdown set to low setting
bAt (Battery type): FLo – Flooded typed
Cb (Maximum current):

Cb3 – Maximum Shore Power Current draw is 30A