E01

Unit shutdown due to low AC Input
(< 85 +/- 5Vac)

Check AC input source. The unit will
automatically recover when the AC Input
voltage return to > 108 +/-5Vac

E02

Unit shutdown due to high AC
Input (>270 +/- 5Vac)

Check AC input source. The unit will
automatically recover when the AC Input
voltage return to < 260 +/-5Vac

E03

Battery is connected backwards

Check all battery connections

E04

Charger Internal temperature is
too high and unit has shutdown.
Unit will automatically recover
when the unit cools down.

The ventilation of the unit is blocked or
the environmental temperature is high.
Reduce charging current or improve the
ventilation near the unit.

E05

Inlet temperature is high >60°C
(140°F) and unit has shutdown.
Unit will automatically recover
when inlet temperature is reduced
to <45°C (113°F).

Check environmental temperature.
Improve the ventilation around the unit.

E06

High battery temperature >70 °C
(158°C) is sensed by the BTS. The
unit will shutdown. Unit will
automatically recover when battery
temperature has reduced to 60°C
(140°F).

Check battery, charger setting and the
environment the charger is in.

E07

Low battery temperature < -25°C
(-13°F) is sensed by the BTS. The
unit will shutdown. Unit will
automatically recover when battery
temperature reaches -20°C (-4°F).

It is not recommended to charge the
battery at extreme low temperatures.

E08

DC Output fuses are brown.

Check battery connection and replace
fuse with the same type and rating.

E09

Unit shutdown due to high battery
voltage (> 17Vdc). Unit will
automatically recover when battery
temperature reduced to 16Vdc.

Check battery and charger setting.
Check also if there is any other DC
supply connected to the battery banks.