Installation, Power, Control signals – Ransburg Serial Digital Module 76911 User Manual

Page 12: Pneumatic connections, Remote i/o

Advertising
background image

LN-9257-07.1

INSTALLATION

POWER

Connect 24 VDC to J7 Pin-4 and 24 VDC return

(GND) to J7 Pin-3.

CONTROL SIGNALS

1. Discrete 24 V Inputs - Connect individual 24

VDC Inputs to the 8-Pin terminal strip for each

module.

2. Serial Bus via Serial Node Adapter - Connect

Serial Bus output from Serial Node Adapter to

J4 using shielded twisted pair cable, connecting

shield to GND terminal, (+) to (+) and (-) to (-). If

Serial Bus goes onto other motherboards, connect

cable to J10, otherwise connect 120 ohm from

J10 (+) to J10 (-).

PNEUMATIC

CONNECTIONS

Connect supply air to the bottom connector for

each module using 1/4” OD tube. Make connec-

tions to the pneumatic devices being controlled

using 5/32” OD (4mm) tube.

9

Serial Digital Module - Installation

REMOTE I/O

Direct connection to Rockwell/Allen-Bradly

Remote I/O can be made via the Serial Node

Adapter or Serial Node Adapter +. Connect

the Allen-Bradley (AB) RIO cable directly to the

motherboard of the Node Adapter (78145-00 or

LECU4012). If the Serial Digital Module is in the

same motherboard as the Serial Node Adapter

(78145-00), no further connection is necessary.

If the Serial Digital Module is located in a differ-

ent motherboard (78147-00) the local serial bus

must be connected via the connector labeled

“Serial Bus”.